10 CPU Unit Functions
Automatic Transfer at Startup with Parameter File
Use the following file names. The files listed as being required in the right column must be on the Mem-
ory Card to perform automatic transfer at startup.
File type
Program/net-
work symbol file
Parameter file
Data files
*1 Network symbols are supported only for the CJ2H-CPU6@-EIP and CJ2M-CPU3@. If a symbols file (.OBJ) is
transferred to the CJ2H-CPU6@ or CJ2M-CPU3@, A401.03 (Card Transfer Error Flag) will turn ON.
*2 The ATEXECDM.IOM file will be given priority if its contents overlaps with the contents of the
AUTOEXEC.IOM file.
10-32
Exten-
File name
sion
AUTOEXEC
.OBJ
User program
and network
symbols
AUTOEXEC
.STD
• PLC name
• PLC Setup
• I/O tables
• Routing tables
• CPU Bus Unit
Setup Area
AUTOEXEC
.IOM
DM Area data
(Contains the
specified num-
ber of words of
data starting at
D20000.)
ATEXECDM
.IOM
DM Area data
(Contains the
specified num-
ber of words of
data starting at
D0.)
Contents
Description
• Programs in cyclic tasks and inter-
rupt tasks.
*1
• This file must be on the Memory
Card to perform automatic transfer
at startup.
• This parameter files
(AUTOEXEC.STD) must also be
on the Memory Card to perform
automatic transfer at startup.
• Parameter area data for the CPU
Unit
• When the power is turned ON, the
parameters will be automatically
stored in a specified location in
the CPU Unit.
• The user does not need to specify
the data individually in the file.
• The parameter file must be on the
Memory Card to perform auto-
matic transfer at startup when the
program/network symbol file is
AUTOEXEC.OBJ.
• Store the DM Area data starting
from D20000 in the file named
AUTOEXEC.IOM.
• At startup, all data from the start
of the file will be transferred star-
ing at D20000. If there are not
enough words for the entire area,
the remaining words in the area
will not be changed.
• This file is not necessary to per-
form automatic transfer at startup.
• Store the DM Area data starting at
D0 in the file named ATEX-
ECDM.IOM.
• At startup, all data from the start
of the file will be transferred start-
ing at D0. If there are not enough
words for the entire area, the
remaining words in the area will
not be changed.
• This file is not necessary to per-
form automatic transfer at star-
*2
tup.
Required?
Yes
Yes
---
---