Operation from CX-Programmer
1
Right-click the bit for differential monitoring.
2
Click Differential Monitor from the PLC Menu. The Differential Monitor Dialog Box will be dis-
played.
3
Click Rising or Falling.
4
Click the Start button. The buzzer will sound when the specified change is detected and the
count will be incremented.
5
Click the Stop button. Differential monitoring will stop.

10-7-4 Online Editing

The Online Editing function is used to add to or change part of a program in a CPU Unit directly from
the CX-Programmer when the CPU Unit is in MONITOR or PROGRAM mode. One or more program
sections are added or changed at a time from the CX-Programmer. The function is thus designed for
minor program changes without stopping the CPU Unit.
Online editing is possible simultaneously from more than one computer running the CX-Programmer as
long as different tasks are edited.
CX-Programmer
Operating in
MONITOR mode.
SYSMAC
MS
IC101
CJ2H
RUN
IC101
IC101
CPU64 -EIP
ERR/ ALM
NS
INH
COMM
OUT
PROGRAMMABLE
PRPHL
100 M
OUT
OUT
CONTROLLER
COMM
10M
BKUP
OPEN
MCPWR
BUSY
PERIPHERAL
PORT
The cycle time will be increased by from one to several cycle times if the program in the CPU Unit is
edited online in MONITOR mode.
The cycle time will also be increased to back up data in the flash memory after online editing. The
BKUP indicator will be lit during this period. The progress of the backup is displayed on the CX-Pro-
grammer. The delay in the cycle time per cycle will be roughly 1 ms.
There is a limit to the number of edits that can be made consecutively without waiting for backup to be
completed. The actual number depends on the type of editing that is performed, but a guideline of 400
edits can be used.
A message will be displayed on the CX-Programmer if the limit is exceeded, and further editing will not
be possible until the CPU Unit has completed backing up the data. Once backup has been completed,
you can continue online editing again.