Automatic Allocation - Omron CJ2 CPU UNIT SOFTWARE User Manual

Cj2 cpu unit software
Hide thumbs Also See for CJ2 CPU UNIT SOFTWARE:
Table of Contents

Advertisement

8-1-2

Automatic Allocation

Automatic Allocation (Default)
Use this method to allocate I/O according to the status of the connected Units. I/O are allocated auto-
matically, so operations from a Programming Device is not required.
When automatic allocation is used, the I/O allocations will be updated every time the power supply to
the PLC is turned ON.
To change from manual allocation to automatic allocation, delete the I/O tables using a Programming
Device.
The I/O are allocated to the Units
connected when the power supply is turned ON.
Power turned ON
Additional information
Unlike with manual allocation, I/O tables are not created with automatic allocation, and so the
connected Units are not verified.
Allocation Method
With automatic allocations, I/O will be allocated for the connected Units as described in the following
table. No user operation is required.
Unit classification
Basic I/O Units
Special I/O Units
CPU Bus Units
CJ2 CPU Unit Software User's Manual
8 I/O Allocations and Unit Settings
Allocation method
Allocated in order according to location.
Allocated according to front-panel rotary switch settings (i.e., unit
numbers).