10 CPU Unit Functions
Checking the SYNC Indicators on the Fronts of Synchronous Units
The SYNC indicator on the front of a Synchronous Unit will be lit green when the Unit is in Synchro-
nous Unit Operation Mode. This indicator will go out for synchronous output data reception errors
and other errors.
Additional Information
The following bits are allocated to the Synchronous Unit in the Special I/O Unit Area or CPU Bus
Unit Area. This bits can be used in the user programming in the CPU Unit to check and control
the status of the Synchronous Units.
I/O classification
Input bits allocated
in the Special I/O
Unit Area or CPU
Bus Unit Area
(input to CPU Unit)
Output bits allo-
cated in the Special
I/O Unit Area or
CPU Bus Unit Area
(output from CPU
Unit)
Stoppage of Synchronous Unit Operation
Synchronous Signal Monitoring Errors
If the synchronous signal from the CPU Unit to Synchronous Unit is not generated for over 100 ms
during normal operation and 11 s at startup, all Synchronous Units and all synchronous unit opera-
tion will be stopped.
I/O Bus or Synchronous Unit Errors
If even one Synchronous Unit has an I/O bus error or any of the following Unit errors, all Synchro-
nous Units and all synchronous unit operation will be stopped.
• I/O setting error
• Duplicate unit number error
• Special I/O Unit setting error
• CPU Bus Unit setting error
• Special I/O Unit error
• CPU Bus Unit error
A dialog box that shows the error will be displayed on the CX-Programmer.
10-100
Size
Name
1 bit
Synchronous Unit
This flag will be ON while the Synchronous Unit is
Operation Mode
operating in Synchronous Unit Operation Mode. (This
Flag
flag has the same status as the SYNC indicator on the
Synchronous Unit.)
1 bit
Synchronous Data
This flag will be ON if the Synchronous Unit has failed
Receive Warning
to receive synchronous data sent from the CPU Unit
Flag
even one time.
1 bit
Synchronous Data
This flag will be ON if the Synchronous Unit has failed
Receive Error Flag
to receive synchronous data sent from the CPU Unit
two or more times in a row.
1 bit
Synchronous Pro-
This flag will be ON if the internal processing time in
cessing Time Over
the Synchronous Unit has exceeded the synchronous
Flag
operation cycle time one or more times.
1 bit
Unit Error Reset
Turn ON this bit to reset errors, such as synchronous
Bit
data reception errors, in the Synchronous Unit.
1 bit
Unit Warning
Turn ON this bit to reset warnings, such as synchro-
Reset Bit
nous data reception warnings and synchronous pro-
cessing time exceeded warnings, in the Synchronous
Unit.
Function
CJ2 CPU Unit Software User's Manual