Note 1. Refer to the above information on the set values in n066 and set the multiplication rate based
on the reference value. For example, if 5-V output is desired at maximum output frequency
(with n066 set to 0), set n067 to 0.50.
Note 2. The multi-function analog output terminals (AM and AC) have a maximum output of 10 V.

5-11-2 Setting the Pulse Monitor Output (n065 and n150)

• By setting n065 for multi-function analog output type selection to 1 for pulse train output, monitoring
pulse output frequency signals is possible through the multi-function analog output terminals.
• The relationship between the output frequency and pulse train output frequency is set in n150 for mul-
ti-function analog output, pulse train frequency selection.
n065
Multi-function Analog Output Type
Selection
Setting
0, 1
range
Set Values
Value
0
Analog voltage output (with monitoring item set in n066)
1
Pulse train output (according to output frequency set in n150)
n150
Multi-function Analog Output,
Pulse Train Frequency Selection
Setting
0, 1, 6, 12, 24, and 36
range
Set Values
Value
0
1,440 Hz at max. frequency (A proportional relationship is applied to frequencies less than
the maximum frequency)
1
1x output frequency
6
6x output frequency
12
12x output frequency
24
24x output frequency
36
36x output frequency
Note The pulse train voltage is 10 V at high level and 0 V at low level at a duty rate of 50%.
Register
0141 Hex
Unit of
1
setting
Description
Register
0197 Hex
Unit of
1
setting
Description
Chapter 5
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0
5-39