10.7
Connecting safety I/O interfaces
Refer to this section before connecting I/O interfaces to external devices.
Source input
This is an input circuit in which the anode of the photocoupler is the input terminal. Transmit signals from a source (open-
collector) type transistor output, relay switch, etc.
The wiring differs depending on the device to be connected and whether the test pulse diagnosis is performed. For the test
pulse diagnosis, refer to "FUNCTIONAL SAFETY" in the following manual. (Rated current: 5 mA, maximum current: 10 mA)
MR-J5 User's Manual (Function)
Connecting an external device
Connect the output signals of the external device to SDI_ _.
24 V DC 5 mA
External device
24 V DC
Control
24 V IN
output 1
Control
0 V IN
output 2
24 V DC 5 mA
Connecting a switch (When the test pulse diagnosis is not performed)
Perform wiring without using PLS_A and PLS_B.
5 mA
Switch
(Test pulse diagnosis disabled)
5 mA
CN3
SDICOMA
SDI1A etc.
Approx. 4.4 kΩ
CN3
SDICOMB
SDI1B etc.
Approx. 4.4 kΩ
CN3
24 V DC ± 10 %
SDICOMA
SDI1A etc.
Approx. 4.4 kΩ
CN3
24 V DC ± 10 %
SDICOMB
SDI1B etc.
Approx. 4.4 kΩ
10 USING FUNCTIONAL SAFETY [G] (MR-J5-_G_-HS_)
10.7 Connecting safety I/O interfaces
10
483