Peripheral equipment

Molded-case circuit breakers, fuses, magnetic contactors
Circuit breakers, fuses, or motor circuit breakers (Type E combination motor controllers) that match the sum of the rated
capacities [kW] of the connected servo amplifiers can be used. The selection conditions are as follows. When using a multi-
axis servo amplifier, calculate the sum of the rated capacities of all axes as the rated capacity of the servo amplifier.
The sum of rated capacities of connected servo amplifiers [kW] ≤ 3 kW (MR-CM3K rated output)
Simple
Total servo
converter
amplifier
capacity
MR-CM3K
Less than 2 kW
2 kW or more
*1 Refer to the following page for compliance with IEC/EN/UL/CSA standards.
Page 340 Molded-case circuit breaker/Semiconductor fuse (simple converter)
Motor circuit breaker (Type E combination motor controller)
Voltage
Sum of rated capacities of
servo amplifiers [kW]
200 V
100 W
system
200 W or less
400 W or less
600 W or less
750 W or less
1 kW or less
2 kW or less
Over 2 kW
Power factor improving AC reactor
Simple converter
MR-CM3K
EMC filter
For selection of EMC filters, refer to the following and the EMC Installation Guidelines.
Page 367 EMC filter (recommended)
Surge protector
Install a surge protector that meets the EMC measures of the servo amplifier to be connected onto the primary (input) side of
the simple converter. PSPD series (manufactured by Okaya Electric Industries) or LT-CS-WS series (manufactured by Soshin
Electric)
*1
Molded-case circuit breaker
Frame, rated current
When a reactor
When a reactor
is not used
is used
30 to 125 A frame
30 to 125 A frame
15 to 20 A
15 to 20 A
30 to 125 A frame
30 to 125 A frame
20 to 30 A
20 to 30 A
Input
Input
rating
phase
[Vac]
200 to 240
3-phase
Fuse
Voltage
Class
Current
AC [V]
[A]
240
T
15 to 30
240
T
40
Motor circuit breaker (Type E combination
motor controller)
Model
Rating [Vac]
MMP-T32
240
Power factor improving AC reactor
FR-HAL-7.5K
6 OPTIONS AND PERIPHERAL EQUIPMENT
Magnetic
contactor
Voltage
AC [V]
AC
DC
power
power
supply
supply
300
S-T21
SD-T21
300
SCCR
[kA]
Rated current
[A]
(heater design)
1.6
50
2.5
4
6.3
6.3
8
18
25
25
6.3 MR-CM simple converter
6
293