Wiring and peripheral options

Wire size
Selection conditions for the wire size are as follows.
Wire type: 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Construction requirements: Single wire set in midair
Between P/+ to P4 and N/- to N-
The following table shows the size of the wire between the FR-XC-(H) and servo amplifier.
Total capacity of servo amplifiers [kW]
1 or less
2
3.5
5
7
11
15
18.5
22
27.5
30
37
45
55
Grounding
The following table shows the size of the grounding wire for the FR-XC-(H). Use the shortest size wire possible.
Multifunction regeneration converter
FR-XC-7.5K
FR-XC-11K
FR-XC-15K
FR-XC-22K
FR-XC-30K
FR-XC-37K
FR-XC-55K
FR-XC-H7.5K
FR-XC-H11K
FR-XC-H15K
FR-XC-H22K
FR-XC-H30K
FR-XC-H37K
FR-XC-H55K
6 OPTIONS AND PERIPHERAL EQUIPMENT
300
6.4 Multifunction regeneration converter (FR-XC-(H))
Wire size [mm
200 V class
2 (14 AWG)
3.5 (12 AWG)
5.5 (10 AWG)
5.5 (10 AWG)
8 (8 AWG)
14 (6 AWG)
22 (4 AWG)
38 (2 AWG)
50 (1/0 AWG)
50 (1/0 AWG)
60 (2/0 AWG)
80 (3/0 AWG)
100 (4/0 AWG)
100 (4/0 AWG)
2
Wire size [mm
]
Rated capacity of multifunction
regeneration converter ≥ Total capacity of
connected servo amplifiers × 2
8 (8 AWG)
8 (8 AWG)
8 (8 AWG)
22 (4 AWG)
22 (4 AWG)
38 (2 AWG)
38 (2 AWG)
3.5 (12 AWG)
3.5 (12 AWG)
3.5 (12 AWG)
8 (8 AWG)
8 (8 AWG)
14 (6 AWG)
14 (6 AWG)
2
]
400 V class
2 (14 AWG)
2 (14 AWG)
3.5 (12 AWG)
5.5 (10 AWG)
5.5 (10 AWG)
8 (8 AWG)
8 (8 AWG)
8 (8 AWG)
14 (6 AWG)
22 (4 AWG)
22 (4 AWG)
38 (2 AWG)
38 (2 AWG)
50 (1/0 AWG)
Rated capacity of multifunction
regeneration converter < Total capacity of
connected servo amplifiers × 2
8 (8 AWG)
14 (6 AWG)
22 (4 AWG)
38 (2 AWG)
38 (2 AWG)
60 (2/0 AWG)
80 (3/0 AWG)
3.5 (12 AWG)
5.5 (10 AWG)
8 (8 AWG)
14 (6 AWG)
22 (4 AWG)
22 (4 AWG)
38 (2 AWG)