Noise Reduction Techniques - Mitsubishi Electric MELSERVO MR-J5 Series User Manual

Ac servo system
Hide thumbs Also See for MELSERVO MR-J5 Series:
Table of Contents

Advertisement

10.9

Noise reduction techniques

This section provides information on measures that prevent the servo amplifier malfunctioning when it is installed next to
peripheral devices that emit a large amount of noise.
Ground shielded cables close to the servo amplifier. Ensure that the part of the cable before the grounding point does not
induce electromagnetic noise to the section of the cable after the grounding point. Strip part of the shielded cable, then ground
the exposed portion of the cable on a large surface of the cabinet. A metal cable clamp can also be used to ground the cable
(shown below). Mask the painted internal wall of the cabinet that touches the cable clamp.
• Exposed shield
Shielded part
• Grounding the shield
Masked paint
part
Ground both ends of the cable of the CN3 safety signal with the cable clamp. The shield length from the servo amplifier to the
cable clamp should be within 30 cm.
Servo
amplifier
CN3
Cable
clamp
For the grounding of the shield of the I/O signal cable, SCC 15-F (Phoenix Contact) can be used. Refer to the following for
details.
Page 410 SCC 15-F Shield connection clamp
10 USING FUNCTIONAL SAFETY [G] (MR-J5-_G_-HS_)
490
10.9 Noise reduction techniques
Screw
Clamp fitting
Shielded cable
Inside
the cabinet
30 cm or less

Advertisement

Table of Contents
loading

Table of Contents