Air Filter Installation - Trane 4YCC4024E1060 Installation And Operation Manual

Single packaged gas/electric 13.4 seer2 convertible, 2 - 5 ton
Table of Contents

Advertisement

H H i i g g h h A A l l t t i i t t u u d d e e I I n n s s t t a a l l l l a a t t i i o o n n
Input ratings (BTUH) of these furnaces are based on
sea level operation and should not be changed at
elevations up to 2000 ft. If the unit installation is from
Table 12. Orifice Twist Drill Size
Orifice Twist
Drill Size if
Installed at
2000
Sea Level
32
33
33
35
37
38
49
50
52
52
Table 13. Orifice Part Numbers
Part
Drill Size
Number
32
ORF01307
33
ORF0134
34
ORF01335
35
ORF01407
36
ORF01408
37
ORF01406
38
ORF01306
39
ORF01409
40
ORF01336

Air Filter Installation

The packaged unit requires an air filter. The unit does
not come with a factory installed filter rack in it,
however, two filter frame accessories are offered that
will allow the installation of a filter within the unit,
BAYFLTR101 & BAYFLTR201. Otherwise a field
supplied filter rack must be installed by the installer in
the return duct work.
18-EB40D1-1C-EN
Altitude Above Sea Level and Orifice Change Required for that Elevation
3000
4000
34
35
35
36
39
39
50
50
53
53
From National Fuel Gas Code — Table F-4
Part
Drill Size
Number
41
ORF01413
42
ORF01410
49
ORF01333
50
ORF01332
51
ORF01336
52
ORF01331
53
ORF01411
54
ORF01412
2000 to 8000 feet elevation, then change the burner
orifices to the size listed in
Table 13, p. 21
for orifice part numbers.
5000
6000
35
36
36
37
40
41
51
51
53
53
Affix the filter label supplied with the unit adjacent to
the filter area. Refer to
Table 14, p. 21
filter size.
Table 14. Determine Filter Size
Nominal
Unit
CFM
YC~4024A
800
YC~4030A
1000
YC~4036A
1200
YC~4042A
1400
YC~4048A
1600
YC~4060A
2000
Filters must be installed in the return air system. The above square
(a)
footages are based on 300 F.P.M. face velocity. If permanent filters
are used, size per mfg. Recommendation with clear resistance of
0.05" WC.
I I m m p p o o r r t t a a n n t t : : Air filters and media wheels or plates shall
meet the test requirements in UL 900.
U U n n i i t t I I n n s s t t a a l l l l a a t t i i o o n n
Table 12, p.
21. Refer to
7000
8000
36
37
38
38
42
42
51
52
53
54
to determine
Filter
(a)
Filter Size
Resistance
(Sq Ft)
(W.C.)
2.67
0.08
3.33
0.08
4.00
0.08
4.67
0.08
5.33
0.08
6.67
0.08
21