Method: Method #2; Communicating Mode - Trane TAMXB0A24V21DB Installation, Operation And Maintenance Manual

Variable speed air handlers convertible 2 - 5 ton
Table of Contents

Advertisement

Button Press AHC Configuration Method: Method #2
Table 25. Configuration for Replacement AHC
Replacement AHC will need to be configured for unit size. Airflow will be set at 400 cfm/ton based on unit size configuration. These
configurations can be done through the Diagnostics Mobile App with no manual steps or can be done manually without the Diagnostics Mobile
App.
Step
Manual Program Unit Model Size
1
Hold J13 BLE button down for 5 seconds and release
2
Now entering programming
3
If a configuration is present, will announce now
4
If no configuration is present, AHC will inform you it is ready to
program
5
After 5 quick flashes, start programming within 2 seconds by
pressing J13 button. Red LED will also flash with each button
press
6
2 seconds after the last button press, the Red LED will flash 1
time to acknowledge programming
7
If the configuration is correct and the BLE button has not been
pressed for 2 seconds, Red LED will announce successful
programming
Replacement AHC configuration — LINK Communicating Mode:
The system controller (SC360) will load important parameters in communicating mode and no interaction is necessary when replacing the AHC.
IF the AHC and the System Controller (SC360) need replaced at the same time- contact your local FSR or technical support agent.
42
Red LED Status
Red LED will be off
1 Red LED flash alerts user that it is now able to program
Red LED will be off if no configuration is present
5 quick Red LED flashes
1 press= TAMXB0A24
2 press= TAMXB0B30
3 press= TAMXB0C36
4 press= TAMXB0C42
5 press= TAMXB0C48
6 press= TAMXB0C60
Red LED will now flash the number of times you pressed to
confirm your configuration. If you programmed the wrong size,
within 2 seconds, start step 5 over
Red LED will turn on for 5 seconds announcing the
configuration has been stored in NV memory correctly. Red LED
will be on for only 2 seconds if not stored properly.
Programming is complete.
18-GJ89D1-1F-EN

Advertisement

Table of Contents
loading

Table of Contents