General Information

General Information

Operating Environment

The Performance Climate Changer™ air handler is a
central station air handler for indoor and outdoor
applications. When considering the placement of the air
handler, it is important to consider the operating
environment. The acceptable ambient temperature range
for unit operation is -40ºF to 140ºF (-40ºC to 60ºC).
For heating applications, a special motor may be required
to withstand the higher temperatures. Motors with Class B
insulation are acceptable for ambient temperatures up to
104º F, while motors with Class F insulation can withstand
ambient temperatures to +140º F (60º C).
Note: Units with UL approval have a maximum ambient
temperature requirement of 104ºF. The customer
should provide adequate freeze protection for the
coils. See
"Routine Maintenance," p. 143
information.

Unit Description

The Performance Climate Changer air handler is designed
for a variety of controlled-air applications. The basic unit
consists of a fan, heating and/or cooling coils, filters, and
dampers.

Components

Trane air handlers ship as complete assemblies or in sub-
assemblies if shipping splits are required. Some assembly
is required when the unit ships in subassemblies.
A wide variety of components is available for Trane air
handlers, including numerous fan, coil, and filter options,
access sections, diffusers, discharge plenums, face-and-
bypass sections, UL-approved electric heat sections,
humidity management options, energy recovery options,
mixing boxes, moisture eliminator sections, exhaust
dampers, controls, blenders and airflow monitoring
stations.
For more information, refer to the following documents,
available from your local Trane sales engineer:
CLCH-PRC022*-EN, Performance Climate Changer™
Air Handler catalog
CLCH-PRC023*-EN, Performance Climate Changer™
Air Handler dimensions
CLCH-PRC016-EN, Performance Climate Changer™ Air
Handler quick select
CLCH-SVN05*-EN, Roof Curbs for Performance
Climate Changer™ Air Handlers installation
instructions
CLCH-PRG003-EN, Performance Climate Changer™
Air handler guide specifications
6
CLCH-SLB017-EN, Performance Climate Changer™ Air
Handler sales brochure
CLCH-SVX08*-EN, Gas Heat in Performance Climate
Changer™ Air Handlers installation, operation, and
maintenance guide
CLCH-SVX14*-EN, Performance Climate Changer™
Air Handlers, Inshot Gas Heat installation, operation,
and maintenance
COIL-SVX01*-EN, Coils installation, operation, and
maintenance guide

Factory-Mounted Controls

Trane air handlers are available with a wide selection of
factory-mounted controls, including controllers, motor
starters, and variable frequency drives (VFD).
Most control components are mounted inside the unit.
for more
Depending on the system configuration, this may include
damper actuators, dirty filter switches, averaging
temperature sensors, and low limit switches. VFDs,
starters, controllers, control transformers, static pressure
transducers, DC power supplies, and customer interface
relays will be in enclosures mounted on the inside of the
unit.
Small items that cannot be factory-mounted, such as
space temperature sensors, outside air temperature
sensors, and humidity sensors, will ship inside the control
enclosures, or packaged and shipped inside the fan or
mixing box section. Larger items are shipped inside the
fan section.
Note: All control valves ship directly to the "ship-to
address" from the vendor unless another address
is given on the Trane sales order.
All factory-mounted control systems (controls that are
factory-wired to a unit controller or termination strip)
ordered without starters or variable-frequency drives
(VFDs) are provided with 120 to 24 Vac control
transformers mounted and wired in the auxiliary control
panel. The customer must provide 120 Vac control power,
50/60 Hz, typically 3 amps for unit sizes 3 to 57 and 5 amps
for unit sizes 66 to 100. A dedicated 15-amp circuit is
recommended.
Factory-mounted control systems ordered with factory-
mounted starters or VFDs are supplied with line to 24 Vac
control transformers. No additional power wiring is
required.
Pre-Packaged Solutions for Controls
If the air handler has been selected using one of Trane's
pre-packaged solutions options for controls, there are a
number of resources available to aid in commissioning
and start-up of the unit. These resources include
commissioning sheets, graphics and technical application
notes. The technical application notes include the control
CLCH-SVX07K-EN