Type K Cooling Coils; Refrigerant Coils - Trane Climate Changer M Series Installation Operation & Maintenance

Air handlers unit sizes 3 to 120
Table of Contents

Advertisement

Routine Maintenance
6. Spray the leaving air side of the coil first, then the entering air side.
7. Thoroughly rinse both sides of the coil and the drain pan with cool, clean water.
8. Repeat steps 6 and 7 as necessary.
9. Straighten any coil fins that may have been damaged during the cleaning process.
10. Confirm the drain line is open following the cleaning process.
11. Allow the unit to dry thoroughly before putting it back into service.
12. Replace all panels and parts and restore electrical power to the unit.
13. Be careful any contaminated material does not contact other areas of the unit or building.

Type K Cooling Coils

Type K cooling coils have removable headers for cleaning:
1. Remove the headers.
2. Use a small nylon or fiber brush to clean the tubes.
3. Flush the tubes with water.
4. Install a new rubber sealing gasket and be sure it seats properly when the header is replaced.
Note: Apply washers under the bolt heads. Bolts should be evenly tightened to 50 foot-pounds of

Refrigerant Coils

Hazardous Pressures!
Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution
temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety
precautions could result in coil bursting, which could result in death or serious injury.
To clean refrigerant coils:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate personal protective equipment, use a soft brush to remove loose
3. Install a block-off to prevent spray from going through the coil and into a dry section of the unit
4. Mix a high-quality coil cleaning detergent with water according to the manufacturer's
Note: If the detergent is strongly alkaline after mixing (PH 8.5 or higher), it must contain an
88
Properly dispose of all contaminated materials.
torque, beginning in the center and working toward the outside.
WARNING
debris from both sides of the coil.
and/or system ductwork.
instructions.
inhibitor. Follow the cleaning solution manufacturer's instructions regarding the use of the
product.
CLCH-SVX03C-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents