Interrupt
number
High-speed output interrupt 10: the position planning table
I519
instruction completes
I601
Timer interrupts 1 (unit 1ms)
I602
Timer interrupts 1 (unit 1ms)
I603
Timer interrupts 1 (unit 1ms)
I604
Timer interrupts 1 (unit 0.1ms)
Note: When several interrupts occur simultaneously, the interrupt task whose pointer number is smallest is executed
first. The PLC completes the on-going interrupt, and then execute other interrupts according to their pointer numbers.
For example, during the execution of I400 interrupt, if I500 and I300 occur simultaneously, the PLC executes the I300
interrupt (smaller pointer number) after executing the I400 interrupt.