AS Ser ies Pro gra mm in g M anu al
4.
When the current value of C10 is between the minimum value and the maximum value, M10–M13 are ON.
Otherwise, M10–M13 are OFF.
Minimum value
D100=40
D102=120
_6
D104=140
D106=150
5.
Suppose the minimum value is larger than the maximum value. When the current value of C10 is less than the
maximum value (C10<60), or when the current value of C10 is larger than the minimum value (C10>140), M12 is
ON. Otherwise, M12 is OFF.
Minimum value
D100=40
D102=120
D104=140
D106=150
6 - 1 9 4
Maximum value
Current value of C10
D101=100
40≦C10≦100
120≦C10≦210
D103=210
140≦C10≦170
D105=170
150≦C10≦390
D107=390
Maximum value
Current value of C10
40≦C10≦100
D101=100
120≦C10≦210
D103=210
60≦C10≦140
D105=60
D107=390
150≦C10≦390
Output
M10=ON
M11=ON
M12=ON
M13=ON
Output
M10=ON
M11=ON
M12=OFF
M13=ON