Connecting Turnback Cables

Recommended Power
Supplies
Recommended Wire
Strip Length
Pin Terminal Length
3-3
Connecting Turnback Cables
Note
40
Use the following screwdriver or an equivalent to remove the wires.
Recommended Screwdriver
Model
SZF1
Phoenix Contact
Side view
Front view
0.6 mm
3.5 mm
Use a SELV power supply with overcurrent protection.
A SELV power supply has redundant or increased insulation between the I/O,
an output voltage of 30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-10024 (OMRON) or S82J-10024D
(OMRON)
Type
Stranded wire
20 AWG to 16 AWG
(0.5 to 1.25 mm
Solid wire
Pin terminal
Strip between 7 and 10 mm of insulation at the ends of the wires (stranded or
solid wire).
Strip 7 to 10 mm.
Use pin terminals with a pin (conductor) length of 8 to 10 mm.
Pin length: 8 to 10 mm
When a Slice I/O Terminal is divided into blocks to expand the system, con-
nect a GRT1-TBR Right Turnback Unit to the GRT1-TBL Left Turnback Unit
with a GCN2-100 Turnback Cable.
Power is not supplied through the GCN2-100 Turnback Cable. Always wire
(supply) the power to the GRT1-TBL Left Turnback Unit from the same power
supply that supplies the Communications Unit.
Maker
Gauge
2
)