Temperature Input Units
Step
Input Unit's power supply ON
Wiring for input 1 upper/lower limit
adjustment
Input 1 upper/lower limit adjustment
Change wiring for input 1 bias
compensation
Input 1 bias compensation
Change wiring for input 2
upper/lower limit adjustment
Input 2 upper/lower limit adjustment
Change wiring for input 2 bias
compensation
Input 2 bias compensation
(End of adjustment)
Note The terminal block temperature stabilization time does not affect the
upper/lower limit adjustment, so the adjustment can be performed immedi-
ately if 30 minutes have passed since the Temperature Input Terminal's
power was turned ON.
Timing chart
Wait at least 30 minutes.
(Check whether additional
time is required for devices
such as the STV, DMM,
and ZERO-CON.)
60 minutes min.
60 minutes min.
Section 6-4
Stabilization time
Temperature
Input Terminal's
stabilization time
Terminal Block temperature
stabilization time 1 after wiring
is changed.
Terminal Block temperature
stabilization time 2 after wiring
is changed
219