Other Errors
Status
After replacing an Analog
Input Unit or Temperature
Input Units, the TS indicator
on the Communications Unit
flashes red and the TS indica-
tor on the replaced Unit lights
red. The TS indicator on the
Slice I/O Unit to the left of the
replaced Unit is light green
and TS indicator on the Unit
on the right is not lit.
After replacing an I/O Unit, the
TS indicator on the Communi-
cations Unit lights red and the
TS indicator on the replaced
Unit lights red. The TS indica-
tor on other I/O Unit flash red.
292
The indicator status shown below will occur when the registration table has been created
or data has been backed up and then an I/O Unit other than an Analog Input Unit or Tem-
perature Input Unit is replaced with an Analog Input Unit or Temperature Input Unit. It will
also occur when an Analog Input Unit or Temperature Input Unit is replaced with a differ-
ent model of Analog Input Unit or Temperature Input Unit.
Check the model of the I/O Unit. When replacing a Unit, always replace it with the same
model. After replacing the Unit, turn the power supply OFF and ON.
Communications Unit
LED Indicators
On left of
replaced Unit
The indicator status shown below will occur when the registration table has been created
or data has been backed up and then an I/O Unit is replaced with a different model of I/O
Unit (but not an Analog Input Unit or Temperature Input Unit).
Check the model of the I/O Unit. When replacing a Unit, always replace it with the same
model. After replacing the Unit, turn the power supply OFF and ON.
Communications Unit
LED Indicators
Replaced Unit (not an Analog
Input or Temperature Input Unit)
Likely cause and remedy
I/O Units
On right of
replaced Unit
Replaced Analog Input or
Temperature Input Unit
I/O Units
Section 9-4
End Unit
End Unit