Analog Input Units
I/O Data
Analog Data
Top/Valley Detection
Timing Flags (Shot Status)
3. Open the tab page for the input for which analog data is to be selected, and
select from the pull-down list the type of data to be allocated to Analog Da-
ta.
4. Return to the General Tab Page, click the Download Button and then click
the Reset Button to reset the Unit.
5. Click the OK Button to exit.
Analog data is used to monitor analog values. Analog input value is allocated
as the default setting, but any one of analog input value, peak value, bottom
value, top value, valley value or rate of change can be selected as allocation
data.
Note The comparator function can be used for the data allocated in Analog Data.
The data format used for allocating data in the Master is shown below. Data is
allocated as two's complements (4 bytes = 2 words).
15
These flags turn ON for the one-shot time when detecting the top or valley for
the top/valley hold function.
These flags are used to time reading the values held as the top and valley val-
ues at the Master. The following data format is used when these flags are
allocated in the Master (2 bytes/1 word).
Bit 7
+0
0
+1
0
Analog Data for Input 0
Analog Data for Input 1
Bit 6
Bit 5
Bit 4
0
0
0
0
0
0
Section 5-4
0
Bit 3
Bit 2
Bit 1
0
0
V_ST1
0
0
T_ST1
Bit 0
V_ST0
T_ST0
109