Temperature Input Units
One-shot Time Setting
1,2,3...
Top/Valley Counter
Function
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1. Input the desired value in the SHOT Off Delay Field of the Top/Valley Tab
Page in the Function Choice Area.
2. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
3. Click the OK Button to exit.
This function counts the number of temperature tops or valleys in devices or
applications that have repetitive temperature rises (or drops). A threshold
value can be set for the counter to indicate when preventative maintenance is
required for the Unit or sensors.
The Over Threshold status can be read in the Maintenance Information Win-
dow or by using an explicit message.
Valley Counter Operation
Hold value
Hold Flag
Hold function
starts.
The Valley Count function counts the number
of valleys in the temperature input value.
1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
Temperature
Valley hold
input value
value
Section 6-4
Last value
is held.
Hold function
stops.
197