Omron SmartSlice GRT1-OD4G-1 Operation Manual page 162

Table of Contents

Advertisement

Analog Output Units
Output Range: 1 to 5 V
Output Range: 0 to 10 V
Output Range:
10 to 10 V
Output Range: 4 to 20 mA
142
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 1 to
5 V. The output range is 0.8 to 5.2 V.
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
0000(0)
8000
(−300)
The values 0000 to 1770 hex (0 to 6,000) correspond to the voltage range 0 to
10 V. The output range is
Voltage
10.5 V
10 V
0 V
8000
FED4 (−300)
−0.5 V
0000 (0)
The values F448 to 0BB8 hex (
range
10 to 10 V. The output range is
specified as two's complements (16 bits).
F31C
F448
(−3300)
(−3000)
0000 (0)
8000
The values 0000 to 1770 hex (0 to 6,000) correspond to the current range 4 to
20 mA. The output range is 3.2 to 20.8 mA.
Current
20.8 mA
20 mA
4 mA
3.2 mA
0 mA
FED4
8000
0000(0)
(−300)
1770
189C
(6000)
(6300)
0.5 to 10.5 V.
1770
189C
(6000)
(6300)
3,000 to 3,000) correspond to the voltage
11 to 11 V. Negative voltages are
Voltage
11 V
10 V
0 V
0BB8
0CE4
(3000)
(3300)
−10 V
−11 V
1770
189C
(6000)
(6300)
Section 5-5
Conversion data
Hexadecimal (decimal)
7FFF
Conversion data
Hexadecimal (decimal)
7FFF
Conversion data
Hexadecimal (decimal)
7FFF
Conversion data
Hexadecimal (decimal)
7FFF

Hide quick links: