GRT1-CT1(-1) Counter Units
Note
Digital Output (OUT)
Note
236
Item
OFF current
1.0 mA max.
Maximum input signal
60 kHz for pulse/direction counter mode
frequency
60 kHz for up/down counter mode
30 kHz for phase differential counter mode (×1, ×2, or ×4)
Encoder Z Input or Digital Input (IN)
Item
Model
GRT1-CT1
Input type
NPN
Number of inputs
1
ON voltage
15.0 V min. (between input
terminal and V)
ON current
3.0 mA min.
OFF voltage
5.0 V max. (between input
terminal and V)
OFF current
1.0 mA max.
ON response time
1 ms max. (See note)
OFF response time
1 ms max. (See note)
The response time is the time between the moment the A, B, or Z/IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
Item
Model
GRT1-CT1
Output type
NPN
Number of outputs
1
Total output current
500 mA max.
Residual voltage
1.2 V max. (between output
terminal and G)
Leakage current
0.1 mA max.
ON response time
1 ms max. (See note)
OFF response time
1 ms max. (See note)
The response time is the time between the moment the A, B, Z, or IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
Section 7-4
Specification
Specification
GRT1-CT1-1
PNP
15.0 V min. (between input
terminal and G)
5.0 V max. (between input
terminal and G)
Specification
GRT1-CT1-1
PNP
1.2 V max. (between output
terminal and V)
0.1 mA max.