Temperature Input Units
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
190
upper limit is 7FFE hex and the lower limit is 8000 hex. (In 1/100 Display
Mode the upper limit is 7FFFFFFE hex and the lower limit is 80000000 hex.)
Upper limit 7FFE
100% scaling value
0% scaling
1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select Pa-
rameters - Edit. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the I/O Module Tab
Page.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where scaling is to be performed, and se-
lect the Scaling Check Box in the Function Choice Area.
Offset value
(–28,000 to
28,000)
100%
0%
Section 6-4
Scaled line
Input signal range