Omron SmartSlice GRT1-OD4G-1 Operation Manual page 81

Table of Contents

Advertisement

Maintenance Information Window
Tabs in the Maintenance Information Window
General Tab Page
Item
Comment
Displays up to 32 characters of text set as the Unit comment.
Last Maintenance
Displays the last maintenance date that was set.
Date
Unit Conduction
Displays the total time that the Unit has been ON (cumulative
Time
power ON time).
Update Button
Click this Button to update the Maintenance information.
Save Maintenance
This function saves the maintenance counter value in the Unit.
Counter
If this function is used, the previous value will be retained
when the power supply is turned OFF and ON again.
Status Check Boxes for Status Flags
The flags shown in the following table will be turned ON when the correspond-
ing error occurs.
Item
Unit Maintenance
ON when the total Unit ON time exceeds the set value.
Also turns ON when the Unit ON time exceeds 87672 hours
(10 years).
Connected Device
ON when any I/O point's Total ON Time Monitor or Contact
Maintenance
Operation Counter exceeds its user-set monitor value.
Operation Time
ON when the measured operation time exceeds the user-set
Monitor
monitor value.
I/O Power Supply
ON when the input power supply is OFF.
Error
EEPROM data error
ON when the data contained in EEPROM is invalid.
Section 4-5
Status check boxes
(Status flags)