Temperature Input Units
Note
1,2,3...
Input type
N
PL2
11. Click the Fix upper adjusting Value Button. The upper limit adjustment
value will be stored in the Unit.
12. To check whether the user adjustment values have been accepted and the
Unit is operating with adjustment values different from the factory defaults,
click the right mouse button over the Slave icon and select Maintenance
Information to open the Maintenance Information Window.
Select the Tab Page for the input that was adjusted. If there is a check in
the User Adjustment Box (bottom right box), the Unit is operating with us-
er-set adjustment values.
1. When checking whether or not the user adjustment values have been set
correctly, always refresh the data by clicking the Update Button in the
Maintenance Information Window's General Tab or uploading the settings
again. For details on the Maintenance Information Window, refer to 6-3
Maintenance Information Window.
2. If the correct reference voltage was not input, the adjustment values may
not be accepted.
Adjusting the GRT1-TS2T's Bias Compensation Value
1. Remove the wiring for upper/lower limit compensation and wiring the Unit
as shown for bias compensation.
2. After completing wiring, wait until the temperature data stabilizes (i.e., until
there is no change in the temperature data for at least 20 minutes). De-
pending on the system setup, this may take over 60 minutes. When the
temperature data is stable, click the Fix Bias adjusting Value Button.
Input voltage
50 mV
50 mV
Section 6-4
217