Omron SmartSlice GRT1-OD4G-1 Operation Manual page 120

Table of Contents

Advertisement

Analog Input Units
Item
Storage temperature
Mounting
Performance Specifications
Item
Input points
Input signal range
Input range setting method
Maximum signal input
Input impedance
Resolution
Overall accuracy
25°C
–10 to 55°C
Analog conversion cycle
AD conversion data
Isolation method
I/O connection method
100
–25 to 65°C (with no icing or condensation)
35-mm DIN Track mounting
Voltage input
2 points (inputs 0 to 1)
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
• DIP switch: Inputs 0 and 1 share the same setting.
• Setting Tool: Inputs 0 to 1 can be set separately.
±15 V
1 M Ω min.
1/6,000 (full scale)
±0.3% FS
±0.6% FS
2 ms max./2 points (when math operations are not used)
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
AD conversion range: ±5% FS of the above data ranges.
Photocoupler isolation (between input and communications lines)
No isolation between input signal wires
Screwless Terminal block
Specifications
Specifications
Current input
0 to 20 mA
4 to 20 mA
±30 mA
Approximately 250 Ω
±0.4% FS
±0.8% FS
Section 5-4