Analog Output Units
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
154
1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the output where the error output value is to be set,
and select the desired item from the pull-down menu in the Fault State
(output during a slice bus error) Field or Idle State (output during a com-
munications error) Field.
5. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
6. Click the OK Button to exit.