Temperature Input Units
Adjustment Procedure for
the GRT1-TS2T
Prepare the devices required for adjustment.
Connect the devices required for adjustment (i.e.,
upper/lower limit adjustment).
Turn ON the power to the related system
devices. Wait at least 30 minutes for the
GRT1-TS2T's internal temperature to stabilize.
Set the input's lower limit adjustment value.
Set the input's upper limit adjustment value.
Remove the devices connected for upper/lower
limit adjustment and connect the devices
require for bias compensation. Wait 60 minutes
for the terminal block temperature to stabilize.
A cold junction compensator and compensating
conductor (e.g., zero conductor) are required
for the thermocouple being adjusted.
Set the input's bias compensation.
Yes
Test indication accuracy after adjustment.
Use the following procedure to adjust the Temperature Input Terminal. Follow
the flowchart closely for proper adjustment.
First
No
adjustment?
Yes
Adjust other
inputs?
No
End
Note The only sensors that can be adjusted are ones that operate while the power
supply is ON. When adjusting for sensors that are not presently in use,
change the input type setting, toggle the power supply or reset the Unit from
the Configurator, and perform the adjustment procedure from the beginning of
the flowchart.
This stabilization time is the time required
when the power is turned ON for the first time.
This step can be skipped when adjusting the
second and following inputs.
Refer to the Operating Manuals for the other
devices in the system for details on their
required stabilization times, if any.