Connecting Turnback Cables

Recommended Power
Supplies
Recommended Wire
Strip Length
Pin Terminal Length
3-3

Connecting Turnback Cables

Note
3-3-1

Connecting Turnback Units

34
Side view
Front view
0.6 mm
3.5 mm
Use a SELV power supply with overcurrent protection.
A SELV power supply has redundant or increased insulation between the I/O,
an output voltage of 30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-10024 (OMRON) or S82J-10024D
(OMRON)
Type
Stranded wire
20 AWG to 16 AWG
(0.5 to 1.25 mm
Solid wire
Pin terminal
Strip between 7 and 10 mm of insulation at the ends of the wires (stranded or
solid wire).
Strip 7 to 10 mm.
Use pin terminals with a pin (conductor) length of 8 to 10 mm.
Pin length: 8 to 10 mm
When a Slice I/O Terminal is divided into blocks to expand the system, con-
nect a GRT1-TBR Right Turnback Unit to the GRT1-TBL Left Turnback Unit
with a GCN2-100 Turnback Cable.
Power is not supplied through the GCN2-100 Turnback Cable. Always wire
(supply) the power to the GRT1-TBL Left Turnback Unit from the same power
supply that supplies the Communications Unit.
Connect Turnback Units with Turnback Cable, as shown in the following dia-
gram. A single Communications Unit can be expanded with up to two sets of
Right/Left Turnback Units.
Gauge
2
)
Section 3-3