Group 9 Communication Parameters - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

Group 9 Communication Parameters

Pr.
Explanation
Communication
09-00
Address
COM1 Transmission
09-01
Speed
COM1 Transmission
09-02
Fault Treatment
COM1 Time-out
09-03
Detection
COM1 Communication
09-04
Protocol
COM2 Transmission
09-05
Speed (Keypad)
COM2 Transmission
09-06
Fault Treatment
(Keypad)
COM2 Time-out
09-07
Detection (Keypad)
COM2 Communication
09-08
Protocol (Keypad)
Response Delay Time 0.0~200.0ms
09-09
Transmission Master
09-10
Frequency
Block Transfer 1
09-11
Block Transfer 2
09-12
Block Transfer 3
09-13
Block Transfer 4
09-14
Block Transfer 5
09-15
Block Transfer 6
09-16
Block Transfer 7
09-17
Block Transfer 8
09-18
Block Transfer 9
09-19
Revision August 2008, 03VE, SW V2.04
Settings
1~254
4.8~115.2Kbps
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operation
0.0~100.0 sec
0: 7N1 (ASCII)
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
4.8~115.2Kbps
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operation
0.0~100.0 sec
0: 7N1 (ASCII)
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
0.00~600.00Hz
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
Chapter 4 Parameters|
Factory
VF
VFPG SVC
Setting
1
9.6
3
0.0
1
9.6
3
0.0
13
2.0
60.00
0
0
0
0
0
0
0
0
0
FOCPG TQRPG
4-21