Emergency Stop (Ef) & Forced Stop Selection - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

Chapter 4 Parameters|
Reverse motor mode
06-12 current limit
External analog terminals
Pr.03-00~02
7: positive torque limit
10: positive/negative torque limit
9: regenerative torque limit
speed
External analog terminals
Pr.03-00~03-02
8: negative torque limit
10: positive/negative torque limit
06-12 current limit
Reverse motor mode
07-36
Emergency Stop (EF) & Forced Stop Selection
Control
VF
VFPG
mode
Settings
When the multi-function input terminal is set to 10 or 18 and it is ON, the AC motor drive will be
operated by Pr.07-36.
4-118
Positive
torque
10: positive/negative torque limit
Pr.07-35
Reverse regenerative
torque limit
Quadrant I
Quadrant II
Quadrant III Quadrant IV
Pr.07-34
Forward regenerative
Reverse motor
torque limit
10: positive/negative torque limit
Negative
torque
SVC
FOCPG TQRPG
0
Coast stop
1
By deceleration Time 1
2
By deceleration Time 2
3
By deceleration Time 3
4
By deceleration Time 4
5
System Deceleration
6
Automatic Deceleration
Forward motor mode
06-12 current limit
External analog terminals
Pr.03-00~02
7: positive torque limit
Pr.07-32
Forward motor
torque limit
Pr.07-33
torque limit
External analog terminals
Pr.03-00~03-02
8: negative torque limit
06-12 current limit
Forward motor mode
The level of torque limit will be
the min. value of following three values
1. torque limit of Pr.07-32 to Pr.07-35
2. Torque limit of external analog terminals
(AVI, ACI and AUI)
3. Pr.06-12 current limit
speed
Factory Setting: 0
Revision August 2008, 03VE, SW V2.04