Chapter 4 Parameters|
05-16

Number of Motor Poles 2

Control
VF
VFPG
mode
Settings
It is used to set the number of motor poles (must be an even number).
05-17

No-load Current of Motor 2

Control
VFPG
SVC
mode
Settings
The factory setting is 40% X rated current.
05-18

Rotor Resistance R1 of Motor 2

Rr of Motor 2

05-19
Control
SVC
FOCPG TQRPG
mode
Settings
05-20
Lm of Motor 2
05-21
Lx of Motor 2
Control
SVC
FOCPG TQRPG
mode
Settings
It will have different setting by the rated current.
05-22
Torque Compensation Time Constant
Control
VF
VFPG
mode
Settings
05-23
Slip Compensation Time Constant
Control
VFPG
SVC
mode
Settings
Setting Pr.05-22 and Pr.05-23 change the response time for the compensation.
When Pr.05-22 and Pr.05-23 are set to 10.00 seconds, its response time for the compensation
will be the longest. But if the settings are too short, unstable system may occur.
4-92
SVC
FOCPG TQRPG
2 to 20
FOCPG TQRPG
0 to factory setting of Pr.05-01
0~65.535Ω
0~6553.5mH
SVC
0.001 to 10.000 sec
0.001 to 10.000 sec
Factory setting: 4
Factory setting: #.##
Factory setting: #.###
Factory setting: #.#
Factory setting: 0.020
Factory setting: 0.100
Revision August 2008, 03VE, SW V2.04
Unit: Amp
Unit: 0.001
Unit: 0.001
Unit: 0.1
Unit: 0.1
Unit: 0.001
Unit: 0.001