Chapter 4 Parameters|

Group 8 High-function PID Parameters

Pr.
Explanation
Input Terminal for PID
08-00
Feedback
08-01 Proportional Gain (P)
08-02 Integral Gain (I)
08-03 Derivative Control (D)
Upper limit for Integral
08-04
Control
PID Output Frequency
08-05
Limit
08-06 PID Offset
08-07 PID Delay Time
Feedback Signal Detection
08-08
Time
08-09 Feedback Fault Treatment
08-10 Sleep Frequency
08-11 Wake-up Frequency
08-12 Sleep Time
08-13 PID Deviation Level
08-14 PID Deviation Time
Filter Time for PID
08-15
Feedback
08-16
|
Reserved
08-20
Tension Control Selection
08-21
Wind Mode
08-22
Mechanical Gear Ratio A
08-23
Mechanical Gear Ratio B
08-24
Source of the Tension
08-25
Command/Line Speed
PID Target Value of
08-26
Tension/Line Speed
Source of Tension/Line
08-27
Speed PID Feedback
Auto-tuning Tension PID
08-28
Tension PID P1
08-29
Tension PID I1
08-30
Reserved
08-31
4-18
Settings
0: No function
1: Negative PID feedback from external terminal AVI
(Pr.03-00)
2: Negative PID feedback from PG card (Pr.10-15, skip
direction)
3: Negative PID feedback from PG card (Pr.10-15)
4: Positive PID feedback from external terminal AVI
(Pr.03-00)
5: Positive PID feedback from PG card (Pr.10-15, skip
direction)
6: Positive PID feedback from PG card (Pr.10-15)
0.0~500.0%
0.00~100.00 sec
0.00~1.00 sec
0.0~100.0%
0.0~110.0%
-100.0~+100.0%
0.0~2.5 sec
0.0~3600.0 sec
0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and keep at last frequency
0.00~600.00Hz
0.00~600.00Hz
0.0~6000.0 sec
1.0~50.0%
0.1~300.0 sec
0.1~300.0 sec
0: Disable
1: Closed-loop, speed mode
2: Line speed, speed mode
3: Reserved
4: Open-loop, torque mode
0: Rewind
1: Unwind
1-65535
1-65535
0: Parameter setting (Pr.08-26)
1: RS-485 communication setting (Pr.08-26)
2: Analog input (Pr. 03-00~03-02 is set to 14 PID target
value of tension, 03-00~03-02 is set to 12 line speed)
0.0~100.0%
0: Analog input (Pr. 03-00~03-02 is set to 11 PID
feedback of tension)
1: Pulse input (Pr.08-40)
0: Disable
1: Reel diameter (08-29~08-31corresponds to 08-44,
08-32~08-34 corresponds to 08-43)
2: Frequency (08-29~08-31 corresponds to 01-07, 08-
32~08-34 corresponds to 01-00)
0.0~1000.0
0.00~500.00 sec
Factory
VF
VFPG
SVC
Setting
0
80.0
1.00
0.00
100.0
100.0
0.0
0.0
0.0
0
0.00
0.00
0.0
10.0
5.0
5.0
0
0
100
100
0
50.0
0
50.0
1.00
Revision August 2008, 03VE, SW V2.04