Response Delay Time; Transmission Master Frequency; Block Transfer 1; Block Transfer 2 - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

Chapter 4 Parameters|
09-09

Response Delay Time

Control
VF
VFPG
mode
Settings
This parameter is the response delay time after AC drive receives communication command
as shown in the following.
RS-485 BUS
09-10

Transmission Master Frequency

Control
VF
VFPG
mode
Settings
When Pr.00-20 is set to 1 (RS485 communication). The AC motor drive will save the last
frequency command into Pr.09-10 when abnormal turn-off or momentary power loss. After re-
power on, it will with the frequency set in Pr.09-10 if there is no new frequency command.
09-11

Block Transfer 1

09-12

Block Transfer 2

09-13
Block Transfer 3
4-148
2
Modbus ASCII mode, protocol <7,E,1>
3
Modbus ASCII mode, protocol <7,O,1>
4
Modbus ASCII mode, protocol <7,E,2>
5
Modbus ASCII mode, protocol <7,O,2>
6
Modbus ASCII mode, protocol <8,N,1>
7
Modbus ASCII mode, protocol <8,N,2>
8
Modbus ASCII mode, protocol <8,E,1>
9
Modbus ASCII mode, protocol <8,O,1>
10
Modbus ASCII mode, protocol <8,E,2>
11
Modbus ASCII mode, protocol <8,O,2>
12
Modbus RTU mode, protocol <8,N,1>
13
Modbus RTU mode, protocol <8,N,2>
14
Modbus RTU mode, protocol <8,E,1>
15
Modbus RTU mode, protocol <8,O,1>
16
Modbus RTU mode, protocol <8,E,2>
17
Modbus RTU mode, protocol <8,O,2>
SVC
FOCPG TQRPG
0.0 ~ 200.0 msec
PC or PLC command
Handling time
of the AC drive
SVC
FOCPG TQRPG
0.00 ~ 600.00 Hz
Response Message
of the AC Drive
Response Delay Time
Pr.09-09
Revision August 2008, 03VE, SW V2.04
Unit: 0.1
Factory Setting: 2.0
Unit: 0.01
Factory Setting: 60.00
Unit: 1
Unit: 1
Unit: 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents