Chapter 4 Parameters|
The Acceleration/Deceleration Time 1, 2, 3, 4 are selected according to the Multi-function Input
Terminals settings. See Pr.02-01 to Pr.02-30 for details.
When enabling torque limit and stall prevention function, actual accel./decel. time will longer
than the above action time.
01-22

JOG Frequency

Control
VF
VFPG
mode
Settings
Both external terminal JOG and key "JOG" on the keypad can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22).
When the jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero.
The used Accel./Decel. time is set by the Jog Accel./Decel. time (Pr.01-20, Pr.01-21).
01-23

1st/4th Accel./decel. Frequency

Control
VF
VFPG
mode
Settings
This parameter selects the frequency point for transition from acceleration/deceleration time 1
to acceleration/deceleration time 4.
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4, may
also be enabled by the external terminals (Pr. 02-01 to 02-08). The external terminal has
priority over Pr. 01-23.
01-24

S-curve for Acceleration Departure Time 1

01-25

S-curve for Acceleration Arrival Time 2

01-26
S-curve for Deceleration Departure Time 1
4-56
Frequency
01-00
Max. O utput
Frequency
Frequency
Setting
accel. time
01-12,14,16,18,20
SVC
FOCPG TQRPG
0.00~600.00Hz
SVC
FOCPG
0.00~600.00Hz
decel. time
01-13,15,17,19,21
Accel./Decel. Time
Time
Factory Setting: 6.00
Factory Setting: 0.00
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Revision August 2008, 03VE, SW V2.04
Unit: 0.01
Unit: 0.01