Accel./Decel. Time Selection Of Stall Prevention At Constant Speed; Over-Torque Detection Selection (Ot1); Over-Torque Detection Level (Ot1) - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

06-05

Accel./Decel. Time Selection of Stall Prevention at Constant Speed

Control
VF
VFPG
mode
Settings
It is used to set the accel./decel. Time selection when stall prevention occurs at constant
speed.
06-06

Over-torque Detection Selection (OT1)

Control
VF
VFPG
mode
Settings
06-07

Over-torque Detection Level (OT1)

Control
VF
VFPG
mode
Revision August 2008, 03VE, SW V2.04
Over-Current Stall
Prevention during
Operation, output
Over-Current
frequency decrease
Detection Level
06-04
over-current stall prevention during operation
SVC
0
by current accel/decel. time
st
1
by the 1
accel/decel. time
nd
2
by the 2
accel/decel. time
rd
3
by the 3
accel/decel. time
th
4
by the 4
accel/decel. time
5
by auto accel/decel. time
SVC
FOCPG TQRPG
0
Over-Torque detection disabled.
1
Over-torque detection during constant speed operation, continue to
operate after detection
2
Over-torque detection during constant speed operation, stop
operation after detection
3
Over-torque detection during operation, continue to operate after
detection
4
Over-torque detection during operation, stop operation after
detection
SVC
FOCPG TQRPG
Chapter 4 Parameters|
Output Current
Output
Frequency
Time
Factory Setting: 150
Factory Setting: 0
Factory Setting: 0
Unit: 1
4-97