01-27

S-curve for Deceleration Arrival Time 2

Control
VF
VFPG
mode
Settings
It is used to give the smoothest transition between speed changes. The accel./decel. curve
can adjust the S-curve of the accel./decel. When it is enabled, the drive will have different
accel./decel. curve by the accel./decel. time.
The S-curve function is disabled when Pr.00-13 is set to 0.
The Actual Accel. Time = selected accel. Time + (Pr.01-24 + Pr.01-25)/2
The Actual Decel. Time = selected decel. Time + (Pr.01-26 + Pr.01-27)/2
01-28

Skip Frequency 1 (upper limit)

01-29
Skip Frequency 1 (lower limit)
01-30

Skip Frequency 2 (upper limit)

01-31
Skip Frequency 2 (lower limit)
01-32
Skip Frequency 3 (upper limit)
01-33
Skip Frequency 3 (lower limit)
Control
VF
VFPG
mode
Settings
These parameters are used to set the skip frequency of the AC drive. The skip frequencies are
useful when a motor has vibration at a specific frequency bandwidth. By skipping this
frequency, the vibration will be avoided.
01-34
Mode Selection when Frequency< Fmin
Control
VF
VFPG
mode
Settings
Revision August 2008, 03VE, SW V2.04
SVC
FOCPG
0.00~25.00 sec /0.00~250.0 sec
Frequency
01-25
01-24
SVC
FOCPG
0.00~600.00Hz
SVC
FOCPG
0
Output Waiting
1
Zero-speed operation
Chapter 4 Parameters|
01-26
01-27
Unit: 0.1/0.01
Factory Setting: 0.2/0.0
Time
Unit: 0.01
Unit: 0.01
Unit: 0.01
Unit: 0.01
Unit: 0.01
Unit: 0.01
Factory Setting: 0.00
Factory Setting: 0
4-57