Chapter 4 Parameters|
Settings
When output current is higher than Pr.02-32, it will activate multi-function output terminal
(Pr.02-11 to Pr.02-14 is set to 27).
When output current is lower than Pr.02-32, it will activate multi-function output terminal
(Pr.02-11 to Pr.02-14 is set to 28).
02-33

Output Boundary for External Terminals

Control
VF
VFPG
mode
Settings
When output frequency is higher than Pr.02-33, it will activate the multi-function terminal
(Pr.02-11 to Pr.02-14 is set to 29).
When output frequency is lower than Pr.02-33, it will activate the multi-function terminal
(Pr.02-11 to Pr.02-14 is set to 30).
02-34

External Operation Control Selection after Reset

Control
VF
VFPG
mode
Settings
After clearing fault once a fault is detected and the external terminal for RUN keeps ON, the
drive can run after pressing RESET key.
02-43

Zero-speed Level of Motor

Control
VF
VFPG
mode
Settings
4-78
0~100%
SVC
FOCPG TQRPG
0.00~+-60.00Hz
SVC
0: Disable
1: Drive runs if run command exists after reset
SVC
FOCPG TQRPG
0~65535rpm
Factory setting: 0.00
Factory setting: 0
Factory setting: 0
Revision August 2008, 03VE, SW V2.04
Unit:0.01
Unit:1
Unit: 1