Chapter 4 Parameters|
N-m
11-06

Gain Value of Flux Weakening Curve for Motor 2

Control
FOCPG
mode
Settings
11-07

Detection Time for Phase-loss

Control
VF
VFPG
mode
Settings
When the phase-loss occurs and exceeds this detection time, the fault code "PHL" will be
displayed. The AC motor drive will record the operation time during phase-loss.
When phase-loss occurs and Pr.11-07 is set to 0, it won't display PHL and won't execute
Pr.06-02.
When user sets this parameter to 0 or not factory setting, we won't promise that all
characteristics will be the same as the 3-phase input.
If it is set to 0 or a larger number, it will short the life of rectifier and capacitors in the AC motor
drive.
11-08
Reserved
11-09
Level of Phase-loss
Control
VF
VFPG
mode
Settings
11-10

Speed Feed Forward Gain

4-162
Flux Weakening Curve
Fbase
0 to 200%
SVC
FOCPG TQRPG
0.01 to 600.00 sec
SVC
FOCPG TQRPG
0.0 to 320.0
11-05/11-06
Hz
Factory Setting: 90
Factory Setting: 0.20
Factory Setting: 60.0
Revision August 2008, 03VE, SW V2.04
Unit: 1
Unit: 0.01
Unit: 0.1
Unit: 1