Chapter 4 Parameters|
00-20

Source of the Master Frequency Command

Control
VF
VFPG
mode
Settings
This parameter determines the drive's master frequency source.
00-21

Source of the Operation Command

Control
VF
VFPG
mode
Settings
When Pr.00-21 is set to 1, it also needs to set Pr.00-20 and Pr.00-21 to 0. After pressing PU
key to make LED PU to be light, RUN, JOG and STOP key are valid now.
00-22

Stop Method

Control
VF
VFPG
mode
Settings
4-48
Output Voltage
100%
The maximum output voltage
reduction is 25%.
75%
Auto Energy-saving Operation
SVC
FOCPG
0
Digital keypad (KPV-CE01)
1
RS-485 serial communication
2
External analog input (Pr. 03-00)
3
External UP/DOWN terminal
4
Pulse input without direction command (Pr.10-15 without direction)
5
Pulse input with direction command (Pr.10-15)
SVC
FOCPG TQRPG
0
Digital keypad (KPV-CE01)
1
External terminals. Keypad STOP disabled.
2
RS-485 serial communication (RJ-11). Keypad STOP disabled.
SVC
FOCPG TQRPG
0
Ramp to stop
1
Coast to stop
Frequency
Factory setting: 0
Factory setting: 0
Factory setting: 0