Description Of Parameter Settings; Group 0 User Parameters - Delta Electronics AC Motor Drive VFD-VE Series User Manual

Vfd-ve series high performance field oriented control ac motor drive
Table of Contents

Advertisement

Chapter 4 Parameters|

4.3 Description of Parameter Settings

Group 0 User Parameters

00-00
Identity Code of the AC Motor Drive
Control
VF
VFPG
mode
Settings
00-01
Rated Current Display of the AC Motor Drive
Control
VF
VFPG
mode
Settings
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
The factory setting is rated current for the constant torque and can be set in Pr.00-12.
kW
0.75
HP
1.0
Pr.00-00
4
Rated Current
for Constant
5
Torque (A)
Rated Current
for Variable
6.3
Torque (A)
Max. Carrier
Frequency
kW
0.75
HP
1.0
Pr.00-00
5
Rated Current
for Constant
3
Torque (A)
Rated Current
for Variable
3.8
Torque (A)
Max. Carrier
Frequency
4-38
: This parameter can be set during operation.
SVC
FOCPG TQRPG
Read Only
SVC
FOCPG TQRPG
Read Only
1.5
2.2
3.7
2.0
3.0
5.0
6
8
10
7.5
11
17
9.4
13.8
21.3
1.5
2.2
3.7
5.5
2.0
3.0
5.0
7.5
7
9
11
13
4.2
6
8.5
13
5.3
7.5
10.6
16.3
15kHz
230V Series
5.5
7.5
11
7.5
10
15
12
14
16
25
33
49
31.3
41.3
61.3
15kHz
460V Series
7.5
11
15
18.5
10
15
20
25
15
17
19
21
18
24
32
38
22.5
30
40
47.5
Factory setting: ##
Factory setting: ##
15
18.5
22
20
25
30
18
20
22
65
75
90
81.3
93.8
113
22
30
37
45
30
40
50
60
23
25
27
29
45
60
73
91
91.3 113.8
56.3
75
9kHz
Revision August 2008, 03VE, SW V2.04
30
37
40
50
24
26
120
146
150
183
9kHz
55
75
75
100
31
33
110
150
138
188
6kHz

Hide quick links: