Ventilation Requirements - HP A6604 Installation Manual

Table of Contents

Advertisement

Table 3-2 Limitation on dust concentration and diameter in the equipment room
Diameter (μm)
Concentration limit
3
(particles/m
)
Concentration limit of harmful gases
Besides, the contents of salt, acid, and sulfide in the equipment room of the router should be
strictly restricted. Harmful gases could accelerate the corrosion of metal parts and the aging of
some parts.
Table 3-3
lists the concentration limit of SO
room.
Table 3-3 Concentration limit of some harmful gases in the equipment room
SO
2
H
S
2
NH
3
Cl
2

Ventilation Requirements

The fans of the device draw air in through the inlet vents on the left and out through the
exhaust vents on the right. The fan tray supports automatic fan speed adjustment and hot-
swapping. To ensure good ventilation, make sure that:
There is a minimum clearance of 10 cm (3.94 in.) around the inlet vents and
exhaust vents for heat dissipation of the router chassis.
A ventilation system is available at the installation site.
Figure 3-1 Ventilation method for the device configured with an RPE-X1
0.5
7
1.4 x 10
7 x 10
Gas
1
5
5
2.4 x 10
, H
S, NH
, and CI
in the equipment
2
2
3
2
Max (mg/m
0.2
0.006
0.05
0.01
3
5
5
1.3 x 10
3
)