Powering the Chassis

Powering the BTI7814 Chassis

94
Check the connectivity of the grounding by using a multimeter to measure the
6.
resistance between the shelf and the frame. Put one test lead in contact with an
unpainted zone of the chassis and the other test lead in contact with the equipment
frame. The measured resistance should be less than 1 Ohm.
You have successfully completed this procedure.
Powering the BTI7814 Chassis on page 94
Powering the BTI7802 Chassis on page 100
Powering the BTI7801 Chassis on page 105
Connecting the DC Power Feeds to a BTI7814 DC PEM on page 94
Connecting the AC Power Feeds to a BTI7814 AC PEM on page 97

Connecting the DC Power Feeds to a BTI7814 DC PEM

If you order the BTI7814 chassis with the DC option, the chassis is shipped with the 14-Slot
Chassis DC Power Entry Modules DC PEM installed. This topic describes how to connect
the power feeds to the DC PEMs.