Figure 8: Bti7814 14-Slot Chassis Dc Power Entry Module - Juniper BTI7800 Series Hardware Overview And Installation Manual

Table of Contents

Advertisement

BTI7800 Series Hardware Overview and Installation Guide
External Feeds
A1
B1
A2
B2
42
Each DC PEM features two dual-stud return terminals and two dual-stud feed terminals.
Typically, only one dual-stud terminal is used. The extra dual-stud terminals can be used
for particular applications, such as laboratory applications.

Figure 8: BTI7814 14-Slot Chassis DC Power Entry Module

The DC PEMs are located on the rear of the chassis. The slots are numbered
(from right to left).
PEM 4
PEM 1
PEM 4
power the other set of six channels. For details on the power distribution plan, see
"BTI7814 Power Distribution Plan" on page
There is a direct correlation between the DC PEM slots and the internal shelf input
terminals.
The external
A
feed pair consists of two individual feeds,
the external input terminals of
supply power to the
and
A1
Similarly, the external
B
feed pair consists of two individual feeds,
connect to the external input terminals of
and
PEM 4
supply power to the
This is shown in the following table along with the external breaker requirements for each
individual feed:
DC PEM Slots
PEM 1
PEM 2
PEM 3
PEM 4
and
power one set of six channels, and
PEM 2
40.
and
. The DC outputs of
PEM 1
PEM 3
internal shelf input terminals respectively.
A2
and
PEM 2
PEM 4
B1
and
B2
internal shelf input terminals respectively.
Internal Shelf Input
Terminals
A1
B1
A2
B2
through
PEM 1
PEM 3
A1
and
A2
, which connect to
and
PEM 1
PEM 3
B1
and
B2
, which
. The DC outputs of
PEM 2
External Breaker
Requirements
125A
125A
125A
125A
Copyright © 2019, Juniper Networks, Inc.