Item
Output polarity
Output control
Output period
Gate ON delay
Output time
Timeout
Number of delay
One-shot OR signal
Output time
3.
Tap [OK].
The settings are confirmed and the Parallel window closes.
FZ3 User's Manual
Set value
[Factory
default]
[On at
NG]
Select whether to turn on OR and DO0 to 15 when
On at
judgement result is OK or when it is NG.
OK
Method to output measurement results without synchronizing
[None]
with external devices.
Reference: When "Output Control" Is Set to "None" (p.184)
Method to output measurement results while synchronizing with
Handshaking
external devices.
Reference: When "Output Control" Is Set to "Handshaking" (p.186)
Method to output measurement results while
synchronizing with line processing timing.The STEP
signal is ignored the number of times set in "Number of
Synchronization
delay", and measurement results are output when the
output
STEP signal next turns on.
Reference:
"Synchronization Output" (p.187)
Valid only when "Output control" is set to "None".
Set the cycle by which measurement results are
output.Set the cycle so that the interval is equal to or
2.0 to
higher than "Gate ON delay + Output time" and lower
5000.0 ms
than measurement interval.
[10.0 ms]
If the cycle is longer than the measurement interval,
output timing will be delayed while measurement is
being repeated.
Set the time from when results are output to the parallel
1.0 to
interface to when the GATE signal turns on.Waiting
1000.0 ms
time until data output is stable.
[1.0 ms]
Set this so that it is longer than the external device
delay time.
Valid only when "Output control" is set to "None" or
1.0 to
"Synchronization output".
1000.0 ms
Set the GATE signal ON time.Set the time required for
[5.0 ms]
external devices to acquire measurement results.
Valid only when "Output control" is set to
0.5 to 120.0
"Handshaking".
s
A timeout error occurs when no response from external
[10.0 s]
devices is received within the time that has been set.
Valid only when "Output control" is set to
"Synchronization output".
1 to 15
Set the number of times that the STEP signal turning
[1]
on will be ignored before measurement results of the
STEP signal are output.
ON
Select whether to maintain OR signal output for an
[OFF]
arbitrary amount of time.
0.1 to
Set the OR signal output time.
1000.0 ms
Valid only when "One-shot OR signal" is set to ON.Set
[5.0 ms]
a value that is lower than the measurement time.
Controlling/Outputting through Parallel Communication
Description
When "Output Control" Is Set to
6
179