Inserting An Infeed Unit; Inserting A Space Holder For An Infeed Unit - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.4.4

Inserting an infeed unit

4.4.4.1

Inserting a space holder for an infeed unit

Requirement
● A project has been created.
● The Control Unit is inserted in the device configuration.
Note
Sequence
Generally, the infeed is inserted in the configuration immediately after the drive in the device
view. In this case, the infeed is also automatically wired to the drive (X100).
You can also insert an infeed at a later point in time (for example, after the Motor Module).
The infeed is then no longer automatically wired because the standard interface X100
intended for the infeed is already occupied (e.g. with the Motor Module).
In this case, the device configuration must be changed manually. You can wire the infeed
manually to a free interface (see Section "Editing a DRIVE-CLiQ connection (Page 100)").
You can also change the wiring of the drive object that is currently linked to X100 of the
drive, to a different interface. X100 would then be free again and when the infeed is inserted,
it is automatically linked to X100.
Note
Handling components in the device view is subsequently explained using an infeed as
example. The procedure is identical for all other components.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
4.4 Creating a project offline in Startdrive
Commissioning
91