Comparing Ip Addresses - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
4.5 Establishing an online connection to the drive unit
4.5.3.5

Comparing IP addresses

IP address and the subnet mask in the project
After you have assigned an IP address to the drive, check the IP address and subnet mask
set in the project. An online connection can only be established when the settings in the
project and in the device are identical.
To compare the address, proceed as follows:
1. Search for the drive at "Online access" and "Update accessible devices".
The drive is displayed with IP address and subnet mask.
2. Switch to the device view.
3. Select the PROFINET interface.
4. In the Inspector window, select "Properties " > "General".
5. Click "Ethernet addresses".
The properties of the interface are displayed.
6. Compare the IP address and subnet mask with the settings under "Online access".
Figure 4-51
If both settings are the same, you can establish an online connection.
146
IP address in the project
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1

Advertisement

Table of Contents
loading

Table of Contents