Settings
SS1 with SBR and OFF3
(without encoder)
SS1 with external stop
(with/without encoder)
Example:
Figure 4-99
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Method of operation
In this case, there is no SS1 delay time active. The transition from SS1 to
STO depends entirely on the speed falling below the shutdown speed
(p9560).
Parameters r9773.4 (SBC requested) and r9773.1 (STO selected in the
drive) display the current status of the function.
With external stop, "Safe Stop 1" functions in principle in just the same
way as for "Safe Stop 1 with encoder (time and acceleration-controlled)"
and "Safe Stop 1 without encoder (speed-controlled)". However, note the
following differences:
When SS1 with external stop is selected, the drive is not braked along
the OFF3 ramp: You are responsible in applying suitable measures to
brake the drive. After the delay time has expired (p9556), only
STO/SBC are automatically triggered. After the function has been se-
lected, the delay timer runs down - even if the function is deselected
during this time. In this case, after the delay time has expired, the
STO/SBC function is selected and then again deselected immediately.
The brake ramp (SBR) and the acceleration (SAM) are not monitored
and there is no standstill detection.
With this configuration, STO becomes active after the SS1 timer p9556
has expired; this also applies when SBR has been configured.
Parameters r9773.4 (SBC requested) and r9773.1 (STO selected in the
drive) display the current status of the function.
Safe Stop 1
Commissioning
4.10 Safety Integrated commissioning
237