Calling up the web server configuration
1. In the project navigation, select menu "Drive control > Parameter".
The corresponding detailed view is displayed at the right.
2. In the secondary navigation, call menu "Basic parameterization > Web server".
The detailed view is updated. The settings become active for the web server.
Figure 4-64
Deactivating the web server
The web server is activated as default setting in the configuration. When required, you can
deactivate the web server as follows:
1. In the configuration dialog, deactivate the "Activate" option.
2. Then save the project to accept the settings.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Web server configuration
4.7 Basic parameterization of the drive objects
Commissioning
163