Commissioning
4.10 Safety Integrated commissioning
Setting Safely-Limited Acceleration
Figure 4-110 Example: SLA
1. In field "Acceleration limit" (p9578), enter a value for the acceleration limit for Safely-
Limited Acceleration.
This limit value applies to a positive and negative direction of rotation. The possible
acceleration resolution is shown by the drive in r9790.
2. In the "Stop Response" (p9579) drop-down list, choose the stop response for Safely
Limited Acceleration.
If the SLA subsequently detects violation of the acceleration limit, the drive initiates the
configured stop response.
3. Click the
Figure 4-111 Motor deceleration
Here, you correct the settings for the motor deceleration (see Chapter "SS1 (extended
functions) (Page 236)").
264
icon to open "SS1" screen form.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1